Old Type AC Contactor LC1-D40
1.GENERAL
- 1.1 Certificates: CE;
- 1.2 Electric ratings: AC50/60Hz, 690v, up to 95A;
- 1.3 Application: remote making & breaking circuits, protect circuit from over-load when assembling with thermal over-load relay, frequent start-up and control of AC motor;
- 1.4 Utilization category: AC-3,AC-4;
- 1.5 Altitude:≤2000m;
- 1.6 Ambient temperature: -5℃~+40℃;
- 1.7 Mounting category: IlI;
- 1.8 Mounting conditions: inclination between the mounting plane and the vertical plane
- should not exceed士5°;
- 1.9 Standard: lEC/EN 60947-4-1.
2.TECHNICAL DATA
Items | Model | LC1-D09 ( Z ) | LC1-D12 ( Z ) | LC1-D18 ( Z ) | LC1-D25 ( Z ) | LC1-D32 ( Z ) | ||
Pole | 3/4 | 3/4 | 3 | 3/4 | 3 | |||
Auxiliary Contact | 1NO/1NC | 1NO/1NC | 1NO/1NC | 1NO/1NC | 1NO/1NC | |||
Rated conventional heating current (A) AC-1 | 20 | 20 | 30 | 40 | 50 | |||
Rated operational current (A) |
380/400V | AC-1 AC-4 |
9 | 12 | 18 | 25 | 32 | |
3.5 | 5 | 7.7 | 8.5 | 12 | ||||
660/690V | AC-3 AC-4 |
6.6 | 8.9 | 12 | 18 | 21 | ||
1.5 | 2 | 3.8 | 4.4 | 7.5 | ||||
Rated insulation voltage (V AC) | 690 | 690 | 690 | 690 | 690 | |||
Power of controlled 3-phase cage motor (AC-3) |
KW | 220/230V AC 380/415V AC 660/690V AC |
2.2 | 3 | 4 | 5.5 | 7.5 | |
4 | 5.5 | 7.5 | 11 | 15 | ||||
5.5 | 7.5 | 10 | 15 | 18.5 | ||||
AC coil(V) | 24,36,48,110,127,220,240,380,415,440,480,500,600 | |||||||
DC coil(V) | 24,36,48,110,220 |
Items | Model | LC1-D40 ( Z ) | LC1-D50 ( Z ) | LC1-D65 ( Z ) | LC1-D80 ( Z ) | LC1-D95 ( Z ) | ||
Pole | 3/4 | 3/4 | 3/4 | 3/4 | 3/4 | |||
Auxilirary Circuit Cat:AC-15,Ue=4 15V le=0.95A Ith=10A | 1NO+1NC | 1NO+1NC | 1NO+1NC | 1NO+1NC | 1NO+1NC | |||
Rated conventional heating current (A) AC-1 | 60 | 80 | 80 | 125 | 125 | |||
Rated operational current (A) |
380/400V | AC-3 AC-4 |
40 | 50 | 65 | 80 | 95 | |
18.5 | 24 | 28 | 37 | 44 | ||||
660/690V | AC-3 AC-4 |
34 | 39 | 42 | 49 | 49 | ||
9 | 12 | 14 | 17.3 | 21.3 | ||||
Rated insulation voltage (V AC) | 690 | 690 | 690 | 690 | 690 | |||
Power of controlled 3-phase cage motor (AC-3) |
KW | 220/230V AC 380/415V AC 660/690V AC |
11 | 15 | 18.5 | 5.5 | 25 | |
18.5 | 22 | 30 | 37 | 45 | ||||
30 | 37 | 37 | 45 | 45 | ||||
AC coil(V) | 24,36,48,110,127,220,240,380,415,440,480,500,600 | |||||||
DC coil(V) | 24,36,48,110,220 |
3. ACCESSORIES