C19 CONTACTOR FOR POWER FACTOR CORRECTION

Contact Now

1.General

 

1.1 Electric ratings: AC50/60Hz, up to 400V;
1.2 Standard: IEC/EN 60947-4-1.

 

2.Type Designation

 

 

3. Normal Operation Conditions

 

3.1 Ambient temperature: -5℃~+40℃, the average during 24 hours should not exceed +35°C.
3.2 Altitude:≤2000m;
3.3 Atmosphere conditions: At mounting site, relative humidity not exceed 50% at the max temperature of + 40C, higher relative humidity is allowable under lower temperature. For example, RH could be 90% at +20°C, special measures should be taken to occurrence of dews.
3.4 Pollution degree: 3
3.5 Installation category:Ⅲ
3.6 Installation conditions: the inclination between installation plane and vertical plane is within 土50°
3.7 Impact and shake: the products should locate in the places where there are no obvious impact and shake.

 

4,Technical Data

Modle CJ19-25 CJ19-32 CJ19-43 CJ19-63 CJ19-95
le Rated current le(400V)A 17 23 29 43 63
Power lf controlled capacitor(kVar) 220/230V AC 6 9 10 15 22
380/400V AC 12 18 20 30 40
Rated insulation Vlage Ui (V) 500
Rated operational Voltage Ue (V AC) 380
Restrained surge capacity 20le

 

5. Overall and mounting dimensions(mm)

 

 

Model Amax Bmax Cmax Dmax E F Note
CJ19-25 80 47 124 76 34/35 50/60 Screw mount/35mm rail mount
CJ19-32 90 58 132 86 40 48
CJ19-43 90 58 136 86 40 48
CJ19-63 132 79 150      
CJ19-95 135 87 158      

 

Feedback
Product Recommend