1.General
1.1 Electric ratings: AC50/60Hz, up to 400V;
1.2 Standard: IEC/EN 60947-4-1.
2.Type Designation
3. Normal Operation Conditions
3.1 Ambient temperature: -5℃~+40℃, the average during 24 hours should not exceed +35°C.
3.2 Altitude:≤2000m;
3.3 Atmosphere conditions: At mounting site, relative humidity not exceed 50% at the max temperature of + 40C, higher relative humidity is allowable under lower temperature. For example, RH could be 90% at +20°C, special measures should be taken to occurrence of dews.
3.4 Pollution degree: 3
3.5 Installation category:Ⅲ
3.6 Installation conditions: the inclination between installation plane and vertical plane is within 土50°
3.7 Impact and shake: the products should locate in the places where there are no obvious impact and shake.
4,Technical Data
Modle | CJ19-25 | CJ19-32 | CJ19-43 | CJ19-63 | CJ19-95 | |
le Rated current le(400V)A | 17 | 23 | 29 | 43 | 63 | |
Power lf controlled capacitor(kVar) | 220/230V AC | 6 | 9 | 10 | 15 | 22 |
380/400V AC | 12 | 18 | 20 | 30 | 40 | |
Rated insulation Vlage Ui (V) | 500 | |||||
Rated operational Voltage Ue (V AC) | 380 | |||||
Restrained surge capacity | 20le |
5. Overall and mounting dimensions(mm)
Model | Amax | Bmax | Cmax | Dmax | E | F | Note |
CJ19-25 | 80 | 47 | 124 | 76 | 34/35 | 50/60 | Screw mount/35mm rail mount |
CJ19-32 | 90 | 58 | 132 | 86 | 40 | 48 | |
CJ19-43 | 90 | 58 | 136 | 86 | 40 | 48 | |
CJ19-63 | 132 | 79 | 150 | ||||
CJ19-95 | 135 | 87 | 158 |